Temporal-3 A timing diagram: a line steps up for three equal pulses with equal gaps between them, then stays low for a longer gap

Three beeps and a pause (smoke alarm)

A smoke or fire alarm sounding for smoke or fire. Three beeps and a pause, repeating, is the temporal-3 pattern, the standard emergency evacuation signal.

The pattern Beep, beep, beep, pause; repeating. Each beep and each gap between beeps lasts half a second, and the pause after the third beep lasts 1.5 seconds. The pattern repeats every 4 seconds.

Synthesised from the standard’s timing; real alarms are much louder and the pitch varies by model. A synthesised clip, not a recording. The sound alone (WAV)

Easily confused with

How to read it

The pattern is called temporal-3, or T3. Each beep lasts half a second, with half a second between beeps, and after the third beep there are 1.5 seconds of silence before the next three, so the pattern repeats every 4 seconds. NFPA 72 allows each part 10 percent either way. ANSI S3.41 and ISO 8201 define it as the audible emergency evacuation signal, and UL 217, the standard smoke alarms are tested to, requires a smoke alarm, or a combined smoke and carbon monoxide alarm, to sound it when it detects smoke. Gentex’s manual for its S1209 smoke alarm puts it as “3 beeps, a pause, 3 beeps, a pause”, and NFPA’s Fire Prevention Week tip sheet says three loud beeps mean smoke or fire. The carbon monoxide pattern has four shorter beeps and a longer pause.

Also searched as: fire alarm sound, smoke alarm three beeps, smoke detector beeping 3 times, t3 alarm, temporal 3 pattern, three beeps smoke detector.

These describe what each alarm sound means and which standard sets it. Sounds differ between makers and models, and the alarm’s own manual lists what each of its sounds means. What to do when an alarm sounds is set out by the US Fire Administration at usfa.fema.gov and by your local fire department.

Smoke alarms and building fire alarms

A building’s fire alarm system sounds the same rhythm. NFPA 72 requires it wherever the intended response is to evacuate the building, as Gentex’s manual quotes the code, and New York City’s building code requires it of new fire alarm systems in buildings whose fire safety plan is a total evacuation, the FDNY says. The pattern is the rhythm, not the sound: the FDNY notes that bells, horns or speakers can all sound it.

The pitch of the beeps

No standard sets it. CPSC staff found no requirement in UL 217 for the frequency of a smoke alarm’s horn and say a typical one sounds between 3,000 and 4,000 Hz; the alarm they tested sounded at 3.2 kHz. UL 217 sets the loudness instead: at least 85 dBA, 10 feet from the horn. The clip on this page is synthesised at 3.2 kHz from the standard’s timing, and plays far more quietly. A real alarm may sound higher or lower; the rhythm is what identifies it.

More smoke and CO alarm sounds

The same shape elsewhere